What is BACnet MS/TP?

By Bassirou Thiam, building automation engineer · Updated

BACnet MS/TP (master-slave/token-passing) is the BACnet data link that runs over RS-485 twisted pair, used for field controllers on each floor or system. Master devices pass a token to take turns on the wire. Each trunk connects to the IP backbone through a router.

Limits that shape the design

  • MAC addresses 0 to 127 for masters, unique on the trunk;
  • no more than 32 devices and 4,000 ft per segment without a repeater;
  • around 60 devices per network in practice, depending on traffic;
  • end-of-line termination at both ends, shield grounded at one end.

Details: BACnet addressing.

Sources

  1. KMC Controls, Application Note AN0404A – Planning BACnet networks
  2. Siemens, guide specification Section 23 09 00 – Building Automation System (submittals, network, point naming)